23
Water chillers
LD
PROPELLER
CONDENSER
A I R C O N D I T I O N I N G - R E F R I G E R A T I O N - A I R H A N D L I N G - H E A T E X C H A N G E -
N
N
A
A
0
0
4
4
.
.
5
5
3
3
0
0
A
A
AQUACIAT
100
150
200
250
300
350
400
450
500
600
750
753
900
1000
Compressor
T
ype
SCROLL hermetic
Nomber
1
2
3
4
5
3
4
Rotation speed
rpm
2900
LD - LDC
LDH
Charge R22/R407C
kg
54
9.2
11.5
14.0
19.0
19.0
21
23.5
26.0
30.0
40.0
43
44
53
ILD - ILDH
Charge R22/R407C
12.6
16
20
20
26,5
28
32.5
37,6
57.5
62
62
Capacity control %
100 - 0
100-
50-0
100-
40-0
100-
50-0
100-
70-
30-0
100-
63-
37-0
100-
66-
33-0
100-
70-
40-20-
0
100-
75-
50-25-
0
100-
80-
60-20-
0
100-
66-33-
0
100-
78-
50-28-
0
100-
75-
50-25-
0
Régulator
LD - LDC - LDH
CONNECT
ILD - ILDH
MRS 4.2 A
MRS 3.4 A
CONNECT
Ev
aporator
LD - LDC
LDH
T
ype
Brazed plates
Number
1
2
Water contents
l
1,9
2,85
3,39
5,65
7,5
7,95
9,20
9,70
11,4
16,5
15,8
ILD - ILDH
T
ype
Shell and tube
Brazed plates
Number
1
2
Water contents
l
19
25
33
41
16.5
15.8
Air cooled condenser
T
ype of Fans
Propeller, diameter 760
Propeller, diameter 900
Propeller, diameter 800
Number of Fans
LD LDC
LDH
1
2
3
4
ILD - ILDH
2
3
4
500 rpm
LOW NOISE
Unitary power kW
0,55
0,90
T
otal air flow.
m3/h
LD - LDC
LDH
9360
8200
18540
17340
16100
19240
18750
20520
20080
28770
28050
57110
56700
ILD - ILDH
18540
17340
16100
20920
21780
20870
22440
29530
57110
56700
750 rpm
STANDARD
Unitary power kW
0,9
1,30
T
otal air flow.
m3/h
LD - LDC
LDH
15050
13480
29840
28200
26520
31380
31100
33080
32800
46980
46575
68420
66900
ILD - ILDH
29840
28200
26520
33720
34780
33650
35620
48200
68420
66900
LD
C
(l)
LD
H
Auxiliary capacity
l
160
320
500
Expansion vessel
Capacity
l
18
LDC 18 / LDH 24
24
35
Pressure
bar
1,5
Max.
installation capacity in liters (2)
Hydraulic module (1)
Pure water
- water max 36 °C (3)
1700
2150
2700
5760
- water max 46 °C (3)
900
1100
1900
3523
Glycol water
- water max 36 °C (3)
1200
1500
2250
4230
- water max 46 °C (3)
550
650
1400
2642
Pump standard
ILDH - ILDH - LDC
N°/kW
40/0.75
41/1.15
According to installation requirement (selection in chart)
(1) LDH - LDC - ILDH only
(2) Capacity of the installation as a function of the expansion vessel mounted on the unit.
The auxiliary tank is already taken into account.
In the case where the installation capacity is higher,an expansion vessel must be added on the installation cor-
responding to the surplus capacity.
(3) The water temperatures mentioned are the temperatures which can be reached when the unit is stopped.